Choosing between the MP3000A and MPF300 relay test sets? This comprehensive comparison guide analyzes both models to help power system engineers, substation technicians, and relay testing professionals select the right equipment for their specific needs.

The MP3000A is a high-end universal relay testing system with 6 current outputs and 4 voltage outputs, ideal for complex protective relay commissioning. The MPF300 offers a cost-effective, portable alternative with 3 current channels, perfect for routine substation testing and field applications. Below, we compare specifications, features, applications, pricing, and real-world performance to help you make an informed decision.


Similarities

  • Both can test all types of protection functions.
  • They have four independent AC/DC voltage outputs that have a range of 0-300 VAC, namely VA, VB, VC, and VZ. These outputs have a common neutral.
  •  Fourth voltage VZ  can be independent of VA/VB/VC, or their output can be set as a factor of (VA+VB+VC).
  • All the voltage generators have short circuit protection.
  • All the current generators have open circuit protection.
  • All current/voltage generators are over-temperature protected
  • Both are based on advanced modular plug-in structure.
  • Voltage and current amplifiers are linear.
  • They have Aux dc output
  • They have binary inputs and binary outputs.


Here is a detailed comparison table

Feature/ description MP3000A MPF300
Number of current outputs 6 3
Max ac current range per output 30A 40A
Inbuilt screen  No 7"  800 x 480 color LCD touch screen
External PC/Laptop operation Yes No
Current output power guar 6 x 400VA at 30A, 3 x 700VA at 60A, 1 x 1000VA at 180A Compliance V 21Vpk  3 x 100VA guar at 40A, 1 X 200VA guar at 100A Compliance  V 15pk
Voltage output power guar 4 x75VA at > 100V, 2 x 150VA > 200V  4 x 100VA at 300V, 2 X  70VA> 100V
PC connection Ethernet port 1 RS232 for calibration use
USB support No yes for  file transfer- 2 nos.
Output time > 15 sec at 30A > 10sec at 40A
ApplicationsUniversal/ ComplexStandard
Best forUtilities/larger substationsContractors, routine testing.
SoftwareAdvance( COMTRADE , distance)Standard( Basic tests)